Operation check – APC SmartSlot Series User Manual
Page 7
 
3. Operation Check
1.
Confirm the basic operation of Measure-UPS II. Use the data 
reporting system (see hardware and software compatibility in sec-
tion 1) to confirm that Measure-UPS II is working. With the probe 
(temperature or temperature and humidity) connected to probe 
connector 1, Measure-UPS II should transmit temperature or tem-
perature and humidity values to the reporting system. Note: 
Reported humidity values will be less than 2% RH when using the 
temperature only probe. If the probe is not properly connected 
both temperature and humidity readings will be very low.
2.
Confirm contact sensing by activating each sensor in turn accord-
ing to the sensor manufacturers recommendation. Use the data 
reporting system to verify that each sensor operates as planned.