Chapter 1 Overview

connected between rails to allow for remote capabili-

ties. It is recommended that the split rail connection

not exceed 100 feet. In this configuration the OIT can

communicate with all modules (maximum 16 mod-

ules any combination with one Access module).

RMS

Scanner

RMC

Controller

RMC

Controller

RMS

Scanner

RM

Access

Power

Supply

Slot C

Slot C

Slot C

Slot C

Slot C

Slot

E

OIT

Module Orientation

The picture that follows represents one of several dif-

ferent RM modules. All of them will have four slots

on the face (slot A, B, D, and E) and one on the bot-

tom (slot C) not shown. All of these slots are not al-

ways used on all modules. On the face of the module

there is a button (orange circle) under the zone ad-

dress ([5]). When pushed and held it has the following

functions:
1. For any module, push and hold the orange button

for approximately 3 seconds to change the zone ad-

dress. Valid addresses for Modbus and Standard

bus range from 1 -16 ([1] - [9], [a] is 10, [b] is 11, [C]

is 12, [d] is 13, [e] is 14, [f] is 15, and [h] is 16). The

RMA (Access) module is shipped at address [j] or

17 and is the only module that can have its address

set above 16.

2. When a module is equipped with the Modbus pro-

tocol (RMxxxxxxxxxx1xx) pushing and holding the

orange button for approximately 6 seconds will

cause the LED display to return [P] for protocol.

Releasing the button and then pushing it again

(within 6 seconds) the display will toggle between
[N]

(Modbus) and [S] (Standard Bus).

A

D

E

B

Module Status (Slot A,

B, D, or E)

Protocol (Standard Bus -

red or Modbus - green)

Module outputs 1

through 16, all may or

may not be used depend-

ing on module type