Setup prompts and description, Table 9 – Watlow Series 920 Microprocessor-Based Ramping Control User Manual

Page 43

Advertising
background image

Prompt

Description

ACCESS = (0) CALIB

Range

Default

Your Settings

To enter CALIB parameters, use ACCESS (0) and ENTER.
Tl XX:XX Read only. Displays the Real Time.

HOUR

Enter the hours to display the system time-of-day clock.

0-23 hours

0

MIN Enter the minutes to display the svstem time-of-day clock. 0-59 minutes 0

CAL Enter the Calibration Offset value -90 to 90°F, -50 to 50°C 0
A1H Enter the Alarm 1 High value. Displayed if AUX1 = AL J
Al L Enter the Alarm 1 Low value. Displaved if AUX1 = AL See Below. RAL
A2H

Enter the Alarm 2 High value. Displayed if AUX2 = AL

See Below.

RAH

A2L

Enter the Alarm 2 Low value. Displayed if AUX2 = AL

See Below.

RAL

RETURN Press the ENTER key to returnto the SYSTEM prompt

Press the MODE key to return to the CALIB prompt

Range

AXH J

Process Default Deviation Default

Range

Process Default

Devlatlon Default

& High Slew Limit

!

&

Low Slew Limit

1 382°F/750°C

999°F/555°C/U

AXL J

32°F/O°C

-999°F/-555°C/U

1 Press the MODE key to return to

the PID prompt.

I

I

Prompt

Description

1 Range

Default

1 Your Settings

How To Program the Series 920, Chapter 6

WATLOW Series 920 User’s Manual

43

ifPB H=O. De

Not displayed if OUT = HT or CL

PBC

Enter the Proportional Band value, Cooling.

0 - 900°F/0 - 500°C

45°F/7.22°C

Not displayed if OUT = HT.

RSC

Enter the Reset value, Coollng.

0.00 - 5.00 repeats/minute

0.00

Not dlsplayed if OUT = HT, and PB C = 0.

RTC

Enter the Rate value, Cooling.

0.00 - 5.00 minute

0.00

CTC

Not displayed if OUT = HT, and PB C = 0.

Enter the Cycle Time value, Coding.

5

Not dlsplayed if PB H = 0. Dependent on output & OUT.

RBC Enter the Rate Band value, cooling

0

Not displayed if OUT = CL, and PB C = 0.

0 denotes rate is always functional.

RETURN

Press the ENTER key to return to the SYSTEM prompt