Model number information, Output - control (single or dual), Output - auxiliary – Watlow Series 920 Microprocessor-Based Ramping Control User Manual

Page 60: Duty, Accuracy, Agency approvals, Terminals, Communications, Power, Operating environment

Advertising
background image

l

Offset of input signal, ±90°F (±50°C), ±50 PVU’s, front panel adjustable

±9.0°F (±5.0°C) for 0.l°

units

.

°F, °C, or process variable

units

are user selectable

Output - Control (Single or Dual)

l

Output #2 user selectable as cool action

l

Solid state relay, Form A, 0.5A @ 24VAC minimum, 264VAC maximum,

10mA minimum load, opto isolated, zero cross switching. OFF state
impedance is 20K ohms minimum

.

Open collector, switched DC signal provides a minimum turn ON voltage of
3VDC into a minimum 500 ohm load; maximum ON voltage not greater than
32VDC into an infinite load

l

Electromechanical relay, Form C, SPDT; 6A @ 115/23OVAC, 6A @ 28VDC,

1/8 hp @ 115VAC, 125VA piIot duty @ 115VAC. OFF state impedance is

ohms minimum

l

Triac 15A, resistive @ 23OVAC, 100mA minimum load, mounted external on

rear of case

l

Process, 4-2OmA, non-isolated, load impedance 600 ohms maximum

Output - Auxiliary

l

Electromechanical relay, 2 ea;

#1 ,

Form C; #2 Form A, 6A. SPDT: 6A @

115/230VAC, 6A @ 28VDC 1/8 hp @ 115VAC, 125VA pilot

duty @

1 1 5 V A C .

OFF state impedance is 20K ohms minimum

Accuracy

l

Calibration Accuracy: ±0.15% of span, ± digit at 77°F ±°F (25°C ±3°)
ambient & rated line voltage ± 10%

l

Accuracy Span: 1000°F (540°C) minimum

l

Temperature Stability: ± 2uV°F (3.6uV/°C ambient referred to the input

l

Voltage Stability: ±0.01% of span / % of rated line voltage

Agency Approvals

l

UL recognized, UL873, File #E43684

Terminals

.

#6 compression type, universal bead screw terminals

Communications

l

Serial data communications

l

RS-422A or RS-423A (RS-232C compatible)

l

All operator indication and controls

l

ANSI X3.28 protocol, or XON/XOFF protocol

l

I s o l a t e d

l

DB-15 female receptacle

Power

.

120/240VAC ± 10%, 50/60Hz ±5%.

l

18VA power consumption

l

Data retention upon power failure via nonvolatile memory.

Operating Environment

l

30 to 130°F (0 to 55°C)

l

0 to 90% RH, noncondensing

60

WATLOW Series 920 User’s Manual

Advertising