PID:

PID control:

Proportioning control with auto-reset and rate.

PRG:

set

This parameter determines whether the

ramp as a function of time or ramp rate.

point

Process Variable:

Programmed display

data:

Proportional band:

Proportioning

control:

PWR:

RAH:

RAL:

Rate:

Rate Band:

RB C:

RB H:

RS C:

When ACCESS (1) is entered in the Series 920, the PID

parameters will appear. These parameters consist of Propor-

tional, Integral (auto reset), and Derivative (rate) actions.

Thermal system element to be regulated, such as time

temperature, relative humidity, etc.

will

Displayed information which gives the operator/programmer

the “programmed” or intended process information, i.e.,

intended set point, intended aiarm limit, etc. See "Actual

displayed data”.

The span of temperature about the set point where time

proportional control action takes place.

See Time proportioning control.

Allows the operator to control the outputs manually . Full cool is

-100, 0 is cool and heat off, and 100 is full heat. This parame-
ter takes priority over the LOPWR and HIPWR parameters.

Represents a high limit to set point. The default values are also

the high limits of

your

input type. This parameter will not

appear if DIP switch #7 is ON.

Represents a low limit to set point. The default values

are also

the low limits of your input type. This parameter will not appear

if DIP switch #7 is ON.

Anticipatory action that senses the rate of change of tempera-

ture and compensates to minimize overshoot. Also "deriva-
tive”.

A thermal control band that defines where the rate (derivative

)

function begins. A Watlow rate band occurs centered on set

point at one or more times the width of the proportional band.

The thermal control band for cooling that defines where the

rate (derivative) function begins. This parameter will not

appear if OUT = CL or PBC = 0.

A thermal control band for heating that defines where the rate

(derivative) function begins. This parameter will not appear if

OUT = CL or PBH = 0.

Reset (integral) cooling control action that automatically

eliminates offset, or “droop”, between set point and actual
process temperature in a proportional control. Expressed in

repeats per minute. This parameter will not appear if OUT =
HT or PBC = 0.