Setup menu table, Setup, Setup menu – Watlow Series 93 User Manual

Page 23

Advertising
background image

W a t l o w S e r i e s 9 3

S e t u p

4 . 5

Setup

Parameter

Value

Range

Factory Default

Appears If:

[

`LOC]

0 to 4

0

[``In]

[```J], [```H], [```t], [```n], [```S],

[```J]

DIP switch selectable.

[`rtd], [`r†d], [`0-5], [`420]

[`dEC]

0, 0.0, 0.00

0

[``In] is set to [`0-5] or [`420]

[`C_F]

[```C] or [```F]

Dependent on

[`dFL]

[``In] is set to [```J], [```H],
[```t],[```n],[```S], [`rtd], or
[`r†d]

[``rL]

[``rL] to [``rh]

Input dependent

[``rh]

``rh] to [``rL]

Input dependent

[`Ot1]

[``ht] or [``CL]

[``ht]

[`HSC]

1 to 55, 0.1 to 5.5, 0.01 to 0.55°C

2, 0.2, 0.02°C

1 to 99, 0.1 to 9.9, 0.01 to 0.99°F

3, 0.3, 0.03°F

[`Ot2]

[`Con] Control

[`Con]

[`PrA] Process alarm
[``Pr] Process with no alarm message
[`dEA] Deviation alarm
[``dE] Deviation with no alarm message
[``no] None

[`HSA]

1 to 5555, 0.1 to 555.5, 0.01 to 55.55°C

2, 0.2, 0.02°C

[`Ot2] is not set to [`Con] or [``no]

1 to 9999, 0.1 to 999.9, 0.01 to 99.99°F

3, 0.3, 0.03°F

[`LAt]

[`LAt] or [`nLA]

[`nLA]

[`Ot2] is not set to [`Con] or [``no]

[`SIL]

[``On] or [`OFF]

[`OFF]

[`Ot2] is set to [`dEA] or [``dE]

[`rtd]

[`JIS] or [`din]

[`din]

[``In] is set to [`rtd] or [`r†d]

[`rP`]

[`Str] Ramping on power up

[`OFF]

[``On] Ramping to set point at all times
[`OFF] None

[`rt`]

0 to 9999

100°/hr

[``rP] is not set to [`OFF]

[`P`L]

0 to 100

100

[`Ot1] or [`Ot2] is set to [``ht]

[`dsP]

[`nor] normal

[`nor]

[`SEt] Set Point (lower only)
[`Pro] Process (upper only)

Input Type

Sensor Range Low

Sensor Range High

[```J]

0°C/32°F

750°C/1382°F

[```H]

-200°C/-328°F

1250°C/2282°F

[```t]

-200°C/-328°F

350°C/662°F

[```n]

0°C/32°F

1250°C/2282°F

[```S]

0°C/32°F

1450°C/2642°F

[`rtd]

(1°)

-200°C/-328°F

700°C/1292°F

[`r†d] (0.1°)

-128.8°C/-199.9°F

537.7°C/999.9°F

[`420]

4mA/-999 units

20mA/9999 units

[`0-5]

0VÎ (dc)/-999 units

5VÎ (dc)/9999 units

Table 4.5a -
Input Ranges.

{`dSP}

Table 4.5b -
Setup Menu Prompts and
Descriptions.

Setup Menu

Power Limiting: The power limiting function in % power for heat only. Power
Limiting will function if

[`pb1] is not set to [```0].

Range: Dependent on output type. 0 to 100

Default: 100

Display: Selects which displays are active or viewable. Five seconds after select-
ed, the appropriate display goes blank. Press ‰Advance, ¿Up-arrow or ¯Down-
arrow to override this feature and cause the current value to be displayed for 5
seconds.
Range:

[`nor] Normal displays

Default:

[`nor]

[`SEt] Set Point - lower display only
[`Pro] Process - upper display only

NOTE:

Document your Setup
Menu parameters below.
Do not mark any values
here; make photocopies
instead.

[`P`L]

Advertising