Solid-state relay without contact suppression, Switched dc, Install and wire – Watlow Series 94 User Manual

Page 12: Figure 2.6a, Figure 2.6b

Advertising
background image

Figure 2.6a

– Solid-state Relay Without Contact Suppression

94_ _- 1D K _- 00_ _

0.5 Amp (AC loads only)
Form A

Figure 2.6b –

Switched DC

94_ _- 1D C _ - 00_ _

7

7 to 10VÎ(dc)

unregulated

V—

6

Internal Circuitry

100

External

Load

7

6

-

+

External

Load

7

SS2

SS2

1

Fuse

L1

L2

Customer installed

Quencharc for inductive

loads only. See note 1.

Install and Wire

2 . 6

I n s t a l l a n d W i r e

W a t l o w S e r i e s 9 4

NOTE:

Output is in de-energized
state in Alarm Condition.

NOTE 1:

Switching inductive loads
(relay coils, solenoids,
etc.) with the mechanical
relay, solid-state relay
output options requires
use of an R.C. suppres-
sor.

Watlow carries the R.C.
suppressor Quencharc
brand name, which is a
trademark of ITW
Paktron. Watlow Part No.
0804-0147-0000.

NOTE 2:

When an external device
with a non-isolated circuit
common is connected to
the dc output, you must
use an isolated or un-
grounded thermocouple.

Ó

WARNING: To avoid dam-
age to property and
equipment, and/or injury
or loss of life, use
National Electric Code
(NEC) standard wiring
practices to install and
operate the Series 94.
Failure to do so could
result in such damage,
and/or injury or death.

See note 2.