Setup, Entering the setup menu – Watlow Series 94 User Manual

Page 18

Advertising
background image

4 . 2

S e t u p

W a t l o w S e r i e s 9 4

Setup

[`LOC] Lock
[``In] Input
[`C_F] Celsius - Fahrenheit
[``rL] Range Low
[``rH] Range High
[`Ot1] Output 1
[`HSL] Limit Hysteresis
[`Ot2] Output 2
[`HSA] Hysteresis Alarm*
[`LAT] Latching*
[`SIL] Silencing*
[`rtd] RTD*
[``Up] Upper Display
[`bot] Bottom Display

*

These parameters may be masked or hidden,
depending on the settings of your controller.
For an explanation of when the parameters
will appear, refer to Table 4.5b on page 4.5.

Setup Menu

Press ¿ and ¯ for 3 seconds

Figure 4.2b -
The Setup Menu.

NOTE:

While in the Setup
Menu, all outputs are
off.

The Operation Menu will appear as the default menu of the Series 94. The
Setup Menu displays the parameters that configure the Series 94's features
to your application.

Enter the Setup Menu by pressing the ¿Up-arrow and ¯Down-arrow keys
simultaneously for 3 seconds. The lower display shows the

[`LOC] Lock

parameter, and the upper display shows its current level. All keys are inac-
tive until you release both keys. You can reach the

[`LOC] Lock parameter

from anywhere.

Use the ‰Advance key to move through the menus and the ¿Up-arrow and
¯Down-arrow keys to select data. You will not see all parameters in this
menu, depending on the controller's configuration and model number. If no
keys are pressed for approximately 60 seconds, the controller returns to the
default display.

LIMIT 94

RESET

LIMIT 94

RESET

Figure 4.2a -
Entering the Setup
Menu.

Entering the Setup Menu