A . 1 4

A p p e n d i x

W a t l o w S e r i e s 9 4

Appendix

[`LOC] Lock
[``In] Input
[`C_F] Celsius - Fahrenheit
[``rL] Range Low
[``rH] Range High
[`Ot1] Output 1
[`HSL] Limit Hysteresis
[`Ot2] Output 2*
[`HSA] Hysteresis Alarm*
[`LAT] Latching*
[`SIL] Silencing*
[`rtd] RTD*
[``Up] Upper Display
[`bot] Bottom Display

Setup Menu

Press ¿ and ¯ for 3 seconds

* These parameters may be masked or

hidden, depending on the settings of
your controller. For an explanation of
when the parameters will appear, refer
to Setup Menu table to the right.

[`LLO] Low Limit Set Point*
[`LHI] High Limit Set Point*
[`ALO] Alarm Low*
[`AHI] Alarm High*
[`CAL] Calibration Offset

Operation Menu

* These parameters may be masked or

hidden, depending on the settings of
your controller. For an explanation of
when the parameters will appear, refer
to the Operation Menu table to the right.

Parameter

Value

Range

Factory Default

Appears If:

[`LOC]

0 - 3

0

[``In]

[```J], [```H] (K), [```t], [```n], [```S],

[```J]

DIP switch selectable.

[```b], [`rtd], [`r†d]

[`C_F]

[```C] or [```F]

[```F]

[`LOC] is set to [```0]

[``rL]

[``rL] to [``rh]

Input dependent.

[`LOC] is set to [```0]

[``rh]

``rh] to [``rL]

Input dependent.

[`LOC] is set to [```0]

[`Ot1]

[``HI], [``LO], [`H_L]

[`H_L]

[`LOC] is set to [```0]

[`HSL]

1 - 9999, 0.1 - 999.9°F

3, 0.3°F

[`LOC] is set to [```0]

1 to 5555, 0.1 to 555.5°C

2, 0.2°C

[`Ot2]

[`PrA] = Process Alarm

[``no]

[`LOC] is set to [```0]

[``Pr] = Process with no alarm message
[``no] = None

[`HSA]

1 - 9999, 0.1 - 999.9°F

3, 0.3°F

[`Ot2] is set to [``Pr] or [`PrA] and

1 - 5555, 0.1 - 555.5°C

2, 0.2°C

[`LOC] is set to [```0]

[`LAt]

[`LAt] or [`nLA]

[`nLA]

[`Ot2] is set to [``Pr] or [`PrA] and

[`LOC] is set to [```0]

[`SIL]

[``On] or [`OFF]

[`OFF]

[`Ot2] is set to [``Pr] or [`PrA] and

[`LOC] is set to [```0]

[`rtd]

[`JIS] or [`din]

[`din]

[``In] is set to [`rtd] or [`r†d] and

[`LOC] is set to [```0]

[``UP]

[``no] = no display shown

[`Pro]

[`LOC] is set to [```0]

[`Pro] = Process
[`LoL] = Low limit set point
[`HiL] = High limit set point
[`LoA] = Alarm low set point
[`HiA] = Alarm high set point

[`bot]

[``no] = no display shown

[`HiL]

[`LOC] is set to [```0]

[`Pro] = Process
[`LoL] = Low limit set point
[`HiL] = High limit set point

Setup Menu

Operation Menu

LIMIT

RESET

LIMIT 94

RESET

Enter the Setup Menu by
pressing the ¿Up-arrow and
¯Down-arrow keys simulta-
neously for three seconds. The
lower display shows the
[`LOC] Lock parameter, and
the upper display shows its
current level. All keys are
inactive until you release both
keys. You can reach the
[`LOC] Lock parameter from
anywhere. Use the ‰Advance
key to move through the
menus and the ¿Up-arrow
and ¯Down-arrow keys to
select data. You will not see
all parameters in this menu,
depending on the controller's
configuration and model
number.

Note:
Do not enter any values here;
make photocopies instead.

Operation

Factory

Parameters

Value

Range

Default

Appears If

[`LLO]

[``rL] to [`LHI] or [``rH] if [`LHI] is not active

[``rL]

[`Ot1] is set to [`H_L] or
[``LO] and [`LOC] is not set
to

[```3].

[`LHI]

[`LLO] to [``rH] or [``rL] if [`LLO] is not active

[``rH]

[`Ot1] is set to [`H_L] or
[``HI] and [`LOC] is not set
to

[```3].

[`ALO]

[``rL] to [`AHI] or [``rH] if [`AHI] is not active

[``rL]

[`Ot2] is set to [`PrA] or
[``Pr] and [`LOC] is set to
[```0] or [```1].

[`AHI]

[`ALO] to [``rH] or [``rL] if [`ALO] is not active

[``rH]

[`Ot2] is set to [`PrA] or
[``Pr] and [`LOC] is set to
[```0] or [```1].

[`CAL]

-180°F to 180°F/-100°C to 100°C;

0

[`LOC] is set to [```0] or

or -18.0°F to 18.0°F/-10.0°C to 10.0°C

[```1].