Wa t l o w S e r i e s S D L i m i t

24

C h a p t e r 5 S e t u p

Note: Some values will be rounded off to fit in the four-character display. Full values can be read with Modbus. All temperature parame-
ters are in °F through Modbus.

* Low register numbers contain the two higher bytes; high register numbers contain the two lower bytes of the four-byte integer. Decimal
precision is implied at three decimal places unless otherwise noted.

Display

Parameter Name

Description

Settings

Range

(Integer values for Modbus

in parentheses.)

Default

Modbus*

(less 40,001

offset)

Read/Write

Appears if:

5

Setup Page

[`Sen]
[ SEn]

Sensor Type

Set the analog sensor type.

[``tc] (0)
[`rtd] (1)
[`MA] (2)
[uolt] (3)
[~mu] (5)

[``tc] (0)

70 R/W

Always active.

[`Lin]
[ Lin]

Thermocouple Linearization

Set the analog input thermocouple
linearization.

[```J] J (0)

[```D] D (6)

[```H] K (1)

[Pt11] PTII (7)

[```t] T (2)

[```R] R (8)

[```E] E (3)

[```S] S (9)

[```n] N (4)

[```B] B (10)

[```C] C (5)

[```J] (0)

71 R/W

[`Sen] is set to [``tc].

[`C-F]
[ C-F]

Temperature Units

Set the temperature units for thermocou-
ple and RTD inputs.

[```F] Fahrenheit (0)
[```C] Celsius (1)

[```F] (0)

40 R/W

[`Sen] is set to [``tc]

or

[`rtd].

[S;deC]
[S.dEC]

Temperature Decimal Places

Set the decimal places for the displayed
input value for thermocouple and RTD
types.

[```0] (0)
[``0;0] (1)

[```0] (0)

41 R/W

[`Sen] is set to [``tc]

or

[`rtd].

[P;dEC]
[P.dEC]

Process Decimal Places

Set the decimal places for the displayed
input value for process types.

[```0] (0)
[``0;0] (1)
[`0;00] (2)
[0;000] (3)

[```0] (0)

42 R/W

[``Sen] is set to
[`mA], [uoLt].or
[`mu].

[IS;En]
[IS.En]

INFOSENSE

TM

Enable the sensor feature, which synchro-
nizes the controller with a Watlow sensor.

[``no] (0)
[`Yes] (1)

[``No] (0)

91 R/W

Always active.

[IS;P1]
[IS.P1]

INFOSENSE

TM

1

Set sensor point 1 code.

0 to 999

500

92 R/W

[IS;En] is set to [`yes].

[IS;P2]
[IS.P2]

INFOSENSE

TM

2

Set sensor point 2 code.

0 to 999

500

93 R/W

[IS;En] is set to [`yes].

[IS;P3]
[IS.P3]

INFOSENSE

TM

3

Set sensor point 3 code.

0 to 999

500

94 R/W

[IS;En] is set to [`yes].

[IS;P4]
[IS.P4]

INFOSENSE

TM

4

Set sensor point 4 code.

0 to 999

500

95 R/W

[IS;En] is set to [`yes].

To go to the Setup Page, press both the Up ¿ and Down ¯ keys for three seconds from the Home Page.

[`SEt] will appear in the upper display and [PAgE] will appear in the lower display.

Press the Advance Key ‰ to move through the parameter prompts.

Press the Up ¿ or Down ¯ keys to change the parameter value.

Press the RESET Key at any time to return to the Home Page display.