Wa t l o w S e r i e s S D L i m i t

32

C h a p t e r 7 P r o g r a m m i n g

Display

Parameter Name

Description

Settings

Range

(Integer values for Modbus

in parentheses.)

Default

Modbus*

(less 40,001

offset)

Read/Write

Appears if:

Programming Page

7

The Programming Page allows you to select what parameters appear on the Operations Page. To go to the Pro-
gramming Page, press the Advance ‰ and RESET keys for six seconds from the Home Page. {Prog} will appear in
the upper display and

{page} in the lower display.

Press the Advance Key ‰ to move through the parameter prompts.

Press the Up ¿ or Down ¯ keys to change the parameter value.

Press the Infinity Key ˆ at any time to return to the Home Page.

[~~P1] Parameter Location 1

[L1;Lo] (1)

48 R/W

[~~P2] Parameter Location 2

[L1;Hi] (2)

49 R/W

[~~P3] Parameter Location 3

[L2;Lo] (3)

50 R/W

[~~P4] Parameter Location 4

[L2;Hi] (4)

51 R/W

[~~P5] Parameter Location 5

[A2;Lo] (7)

52 R/W

[~~P6] Parameter Location 6

[A2;hi] (8)

53 R/W

[~~P7] Parameter Location 7

[L3;Lo] (5)

54 R/W

[~~P8] Parameter Location 8

[L3;Hi] (6)

55 R/W

[~~P9] Parameter Location 9

[A3;Hi] (10)

56 R/W

[~P10] Parameter Location 10

[A3;Lo] (9)

57 R/W

[~P11] Parameter Location 11

[none] (0)

58 R/W

[~P12] Parameter Location 12

[none] (0)

59 R/W

[~P13] Parameter Location 13

[none] (0)

60 R/W

[~P14] Parameter Location 14

[none (0)

61 R/W

[~P15] Parameter Location 15

[none] (0)

62 R/W

[~P16] Parameter Location 16

[none] (0)

63 R/W

All parameter locations
always appear on the
Programming Page.

[none] (0) None
[L1;Lo] (1) Limit 1 Low
[L1;hi] (2) Limit 1 High
[L2;;Lo] (3) Limit 2 Low
[L2;hi] (4) Limit 2 High
[L3;;Lo] (5) Limit 3 Low
[L3;hi] (6) Limit 3 High
[A2;Lo] (7) Alarm 2 Low
[A2;hi] (8) Alarm 2 High
[A3;;Lo] (9) Alarm 3 Low
[A3;;hi] (10) Alarm 3 High
[hys1] (11) Alarm Hysteresis 1
(Setup Page)
[hys2] (12) Alarm Hysteresis 2
(Setup Page)
[hyS3] (13) Alarm Hysteresis 3
(Setup Page)
[addr] (14) Modbus Device
Address (Setup Page)
[`C-F] (15) Temperature Units
(Setup Page)
[`CAL] (16) Calibration Offset

Note: All Parameter locations have the same range of possible values.