Component names, Component names -1 – Yokogawa EJA530E User Manual

Page 21

Advertising
background image

<3. Component Names>

3-1

IM 01C25F01-01E

3. Component Names

HIGH

LOW

Slide switch

Burnout direction switch

Write protection switch

Burnout Direction

Switch Position

BO H

L

WR E

D

H

L

H

L

Burnout direction switch (BO)

Burnout Direction

F0301.ai

Write Protection

Switch Position

H

L

E

D

H

L

E

D

Write Protection

Hardware write protection switch (WR)

YES

(Write disabled)

NO

(Write enabled)

External indicator

conduit connection

(Note 1)

Transmitter section

Integral

indicator

(Note 1)

Mounting screw

Range-setting

switch

(Note 1)

(See section 7.5)

Amplifier Cover

CPU assembly

Zero-

adjustment

screw

Conduit

connection

(Note 2)

Note 1: See subsection 9.2, “Model and Suffix Codes,” for details.

Note 2: Applicable for BRAIN/HART communication type. Set the switches as shown in the figure above to set the burn-out direction

and write protection. The Burnout switch is set to the H side for delivery (unless option code /C1 or /C2 is specified in the order),

and the hardware write protection switch is set to E side.The setting of the switches can be confirmed via communication. An

external zero adjustment screw can only be disabled by communication. To disable the screw, set a parameter before activating

the hardware write protect function. See each communication manual.

Figure 3.1

Component Names

Table 3.1

Display Symbol

Display Symbol

Meaning of Display Symbol

The output signal being zero-adjusted is increasing.
The output signal being zero-adjusted is decreasing.

F0302.ai

Write protect function is enabled.

Advertising