<4. Installation>

4-1

IM 01C25F01-01E

4. Installation

4.1 Precautions

Before installing the transmitter, read the cautionary

notes in section 2.4, “Selecting the Installation

Location.” For additional information on the ambient

conditions allowed at the installation location, refer

to section 9.1 “Standard Specifications.”

IMPORTANT

• When welding piping during construction,

take care not to allow welding currents to

flow through the transmitter.

• Do not step on this instrument after

installation.

• For the EJ530 and EJX630A whose

capsule code is A, B or C, the pipe of the

atmospheric opening is located on the

pressure detecting section. The opening

must not face upward. See subsection 5.1.1.

• D capsule of EJ530 and EJX630A is

of sealed gauge reference and the change

in atomospheric pressure may affect the

measurement.

4.2 Mounting

■ The impulse piping connection port of the

transmitter is covered with a plastic cap to

protect against dust. This cap must be removed

before connecting the piping. (Be careful not

to damage the threads when removing these

caps. Do not insert a screw driver or other

tool between the cap and the port threads to

remove the cap.)

■ The transmitter can be mounted on a nominal

50 mm (2-inch) pipe using the mounting bracket

supplied, as shown in Figure 4.1.

■ The user should prepare the mating gasket for

the transmitters with Process connection code

8 and 9. See Figure 4.2.

Horizontal pipe mounting

Vertical pipe mounting

F0401.ai

50 mm (2-inch) pipe

U-bolt (L)

U-bolt (S)

Mounting bracket

U-bolt nut (S)

U-bolt nut (L)

U-bolt nut (L)

Mounting bracket

50 mm (2-inch) pipe

U-bolt (L)

U-bolt (S)

U-bolt nut (S)

Figure 4.1

Transmitter Mounting

Gasket

F0402.ai

Figure 4.2

Gasketing