Programming

17

Step

Comment

CAL 6

Filter.

The filter constant for filtering the input signal.

1

No filtering.

to
99 Very heavy filtering.

CAL 7

Decimal Point for Total Display.

The totals can be displayed with 0, 1, 2 or 3 decimal points.

CAL 8

Total Conversion Factor - whole numbers.

CAL 9

Total Conversion Factor - digits after the decimal point.

The total conversion factor enables the rate to be displayed in
one engineering unit and the totals to be displayed in another
engineering unit. The total conversion factor can be
programmed in the range of 0.000001 - 999,999.

Set to 1.000 if totals and rate are in the same unit, eg. litres.

See Section 3.5.

CAL 10

Low Alarm - whole numbers.

CAL 11

Low Alarm - digits after the decimal point.

CAL 10 to CAL 13 are displayed regardless of whether the
high and low alarms are installed. If the high and low alarms
are not installed, these parameters can be ignored.

CAL 10 & 11 program the flow rate below which the low
alarm relay will close. The value can be programmed in the
range 0 to 999,999.