Yokogawa 202 Field Mounting Rate Totalizer User Manual

Page 8

Advertising
background image

Introduction

4

1.2 INTRINSIC SAFETY CONSIDERATIONS

The Model 202D is certified for use in hazardous areas and has both CENELEC
and CSA NRTL/C approvals.

The Model 202D certification details are:

CENELEC Approval:

Kema 98.E.1873.

Type of Protection:

Ex ia.

Group:

IIB.

Temperature Class:

T4 at ambient temperature of 60

°

C.

CSA NRTL/C Approval
File Number:

LR 104 840-5.

Type:

Class 1, Groups C and D.

When installing in hazardous areas, the instrument must be installed according to
the guidelines in Section 8 and in accordance with standards for wiring and
installation in hazardous areas.

4-20mA/DC Power

The input can be connected to IS circuits with the following maximum values:

Ui = 28V
Ii = 93mA
Pi = 653mW

The internal capacitance and inductance seen on these terminals is 0.1uF and
0mH.