Yokogawa 202 Field Mounting Rate Totalizer User Manual

Page 9

Advertising
background image

Introduction

5

Relay Outputs

The outputs can be connected to IS circuits with the following maximum
values:

Ui = 28V
Ii = 93mA
Pi = 653mW

The internal capacitance and inductance seen on these terminals is 0.1uF and
0mH.

Flowmeter Input

Entity parameters on the flowmeter enable connection to a wide range of
approved sensors.

Input parameters are:

Ui = 24V
Ii = 20mA
Pi = 320mW

The internal capacitance and inductance seen on these terminals is 0.002uF
and 0mH.

Output parameters are:

Uo = 10.0V
Io = 9.0mA

Maximum allowed external capacitance is 60µF.
Maximum allowed external inductance is 1.5H.