The MW100 channels are assigned to the external input channels of the DX as follows:
• Channel Number
The channels of the MW100 selected first are assigned consecutively from external

input channel 201. The channels of the MW100 selected next are assigned to the
available external input channels from the smallest number. You cannot select the
external input channels to be assigned.

MW100

Meas. channels

CH001 to CH020

Meas. channels

CH001 to CH004,

CH011 to CH014

Meas. channels

CH001 to CH030

Order of automatic

assignment

DX

DX external

input channels

MW100

MW100

MW100

CH201

CH220
CH221

CH240
CH241

CH270

MW100 meas.

channels

CH001

CH020
CH001

CH014
CH001

CH030

1

3

2

• Range Settings
The range settings of the MW100 (including the span and unit) are set automatically

to the external input channels.

If the span setting of the MW100 range exceeds the span setting range of the DX

external input channel (–30000 to 30000), it is set to the span upper limit (30000) or
lower limit (–30000).

Specify the settings such as the alarm, tag, and the area display of the color scale band
of each channel after the auto setting is complete.

Note

Precautions When Assigning Channels to the External Input Channels
• The MW100 channels are assigned in unit of 10 channels to the external input channels. If

the MW100 measurement module consists of less than 10 channels, “OFF” is assigned to
the external input channels for the section without channels.

• An error occurs if the number of MW100 channels to be automatically set is greater than the

number of available external input channels.

• If the range setting of a MW100 channel is set to “SKIP,” the external input channel of the

DX is set to “OFF.”

• If a MW100 unit contains a module that cannot be set automatically, only the channels that

can be assigned are assigned to the external input channels of the DX.

• If a new MW100 is added, auto setting is executed again. At this point, all the settings are

cleared. Therefore, you must execute the auto setting again for all MW100s.

• If you are connecting MW100s that can be automatically set and MW100s that cannot

be automatically set or other Modbus devices, automatically set the MW100s that can be
automatically set first and then manually set the connection of the remaining devices.