Note

About the MW100
• MW100s that support auto setting are those with firmware version R2.22 or later.
• MW100 modules that can be automatically set are the following input modules.

4-CH, High-Speed Universal Input Module
10-CH, Medium-Speed Universal Input Module
6-CH, Medium-Speed Four-Wire RTD Resistance Input Module
10-CH, High-speed Input Module

• If there are no channels to be assigned or the Modbus server setting is OFF, auto setting

fails with an error. Check the settings.

• MW100s that are connected through auto setting automatically switches to the measurement

mode.

• Port number 34324 of the MW100 is used to perform auto setting.
• For details on the MW100 settings, see the user’s manual of the MW100.

The first channel information of the MW100 that is automatically set to the external input
channel can be displayed when the cursor is on the first or last channel.

In addition, the status of the connected MW100 can be confirmed on the Modbus status
display screen.