Alarm Output Relay Action When the Alarm ACK Operation Is Executed

You can select the relay output status that is enabled after the alarm ACK operation from
the following two settings.
• Normal: The relay output is deactivated when the alarm ACK operation is executed.

If the condition for activating the alarm output relay is met in the next scan
interval, the relay output is activated.
This operation is valid only when the alarm output relay is set to

Hold.

• Reset: The relay output is deactivated when the alarm ACK operation is executed.

If a new condition for activating the alarm output relay is met, the relay is
activated.

An example of the relay action when alarm ACK is executed is shown below. This
example is for the case when the output relay

AND item is set to OR and the Hold item is

set to

Hold.

• Normal

Alarm ACK

Alarm output relay

Alarm 2

Alarm 1

Relay is activated in the next scan interval

ON

OFF

• Reset

Alarm ACK

Alarm output relay

Alarm 2

Alarm 1

Relay is activated on the next alarm occurrence

ON

OFF

Setup Screen

Press

MENU (switch to the setting mode), hold down FUNC for 3 s (switch to the basic

setting mode), select

Alarm > Switch, Relay

Setup Items

Relay > Relay Action on Ack
Select

Normal or Reset.

Section 3.5, “Setting the Auxiliary Alarm Function” in the user’s manual
Section 3.8, “Releasing the Alarm Output (Alarm ACK Operation)” in the user’s manual
Operation using communication commands: Page 20

Operations on the DX1000/DX1000N/DX2000