6 configuring the system mode, Alarm/relay/remote, 6 configuring the system mode -19 – Yokogawa Data Acquisition with PID Control CX2000 User Manual

Page 31: Alarm/relay/remote -19, Index

Advertising
background image

2-19

IM04L41B01-65EN

1

2

3

4

Index

Viewing and Creating Setup Data

2.6 Configuring the System Mode

Alarm/Relay/Remote

2. Click here (also selectable from [Setting] - [System Mode Setting]).

1. Select this tab.

Remote control

terminal number

Resets the range

selection.
Copy and paste the

selected range

(see page 4-15).

Select actions.

Alarm/Relay

• Reflash

When multiple alarms are set to one alarm output relay, this function notifies the

succeeding alarms after the first alarm that causes the relay activation.

• Relay AND

Set the range of relays (from the first alarm relay) to take the AND logic. All other

relays will be set to OR logic. If [NONE] is selected, all relays will operate using the
OR logic.
• AND: Activated when all alarms are being generated simultaneously.
• OR: Activated when at least one of the alarms is being generated.

• Relay Action

Select whether to energize or de-energize the alarm output relay when the alarm

occurs.

• Alarm Relay Behavior

• Unhold: Turns OFF the output relay when the cause of the alarm is no longer met.
• Hold: Holds the output relay ON until the alarm acknowledge operation is executed.

• Alarm Indicator

Unhold, Hold: See “Alarm Relay Behavior.”

When [Alarm Relay Behavior] is set to [Hold], only [Hold] can be selected for the [Alarm

Indicator].

• Rate of Change Increase/Rate of Change Decrease

Select the time interval for the rate of change alarms in terms of the number of

samplings (1 to 15).

Interval = scan interval × number of samplings

• Alarm Hysteresis

A width (hysteresis) of 0.5% of the display span can be specified on the value used

to set or release the alarm. This applies to upper (H) and lower (L) limit alarms on
measurement channels.

Advertising
This manual is related to the following products: