Setting the Modbus Master

Set the command.

Data type

Select whether or not use command.

Register No. (slave device)

Address (slave device)

Communication input data (DX100P: C01 to C12,

DX200P: C01 to C30)

• Basic

Read cycle: The cycle at which data is read from other devices. Select the read cycle

from [125 ms], [250 ms], [500 ms], [1 s], [5 s], [2 s], or [10 s]

Timeout: Specify a time period that the DXP waits for a response from the specified

slave device after transmitting a command. Select the timeout time from [125 ms], [250
ms], [500 ms], [1 s], [5 s], [2 s], [10 s], or [1 min].

Retrials: The number of times to retransmit the command when there is no response

from the specified slave device. Select the number of retrials from [Off] (0), [1], [2], [3],
[4], [5], [10] or [20].

• Type

• INT16: 16-bit signed integer
• UINT16: 16-bit unsigned integer
• INT32_B: “32-bit signed integer” is assigned to the Modbus register in the order

upper 16 bits followed by the lower 16 bits.

• INT32_L: “32-bit signed integer” is assigned to the Modbus register in the order

lower 16 bits followed by the upper 16 bits.

• UINT32_B: “32-bit unsigned integer” is assigned to the Modbus register in the order

upper 16 bits followed by the lower 16 bits.

• UINT32_L: “32-bit unsigned integer” is assigned to the Modbus register in the order

lower 16 bits followed by the upper 16 bits.

• FLOAT_B: “32-bit floating-point data” is assigned to the Modbus register in the

order upper 16 bits followed by the lower 16 bits.

• FLOAT_L: “32-bit floating-point data” is assigned to the Modbus register in the

order lower 16 bits followed by the upper 16 bits.

2.6 Configuring the System Mode