Fc transmits screen image data, Fe transmits setup data, Fd transmits most recent measured/computed data – Yokogawa Button Operated MV2000 User Manual

Page 114: Ff transmits fifo data

Advertising
background image

4-40

IM MV1000-17E

4.8 Output Commands

(Setting/Measured/

Computed Data Output)

FC

Transmits screen image data

Syntax

FC p1<terminator>

p1 GET (Output the screen image data)

Example Output screen image data from the MV.

FCGET

Description Captures the current MV screen and transmits

the data in PNG format.

FE

Transmits setup data

Syntax

FE p1,p2,p3<terminator>

p1 Output data type

0

Setting commands setup data

1

Decimal place and unit information

2

Basic setting commands setup
data

4

Setup data file

5

Setup channel information output

6

Alarm information output

p2 First channel number (measurement/

computation/external input channel)

p3 Last channel number (measurement/

computation/external input channel)

Example Output the setting commands setup data of

channels 001 to 005 from the MV.

FE0,001,005

Description • Set the first channel number and last channel

number parameters so that the last channel
number is greater than or equal to the first
channel number.

• Parameters p2 and p3 are valid when p1 is set

to 0, 1, 2, 5, or 6. All channels are specified if
parameters p2 and p3 are omitted.

• Set parameters p2 and p3 according to the

table in section 4.3.

FD

Transmits most recent

measured/computed data

Syntax

FD p1,p2,p3<terminator>

p1 Output data type

0

Output the most recent measured/
computed/external input data in
ASCII format

1

Output the most recent measured/
computed/external input data in
binary format

6

Output relay status and internal
switch status

p2 First channel number (measurement/

computation/external input channel)

p3 Last channel number (measurement/

computation/external input channel)

Example Output from the MV the most recent measured/

computed data of channels 001 to 005 in ASCII
format.

FD0,001,005

Description • The most recent measured/computed data

corresponds to the most recent measured/
computed data in the internal memory when
the MV receives the FD command.

• Set the first channel number and last channel

number parameters so that the last channel
number is greater than or equal to the first
channel number.

• Parameters p2 and p3 are valid when p1

is set to 0 or 1. All channels are specified if
parameters p2 and p3 are omitted.

• Set parameters p2 and p3 according to the

table in section 4.3.

FF

Transmits FIFO data

Syntax

FF p1,p2,p3,p4<terminator>

p1 Operation type

GET

Transmit the next block

RESEND Retransmit the previous output

RESET Set the most recent data position

(block) to the read position of the
FIFO buffer (block)

p2 First channel number (measurement/

computation/external input channel)

p3 Last channel number (measurement/

computation/external input channel)

p4 Maximum number of blocks that are to be

loaded

1200

MV1004/MV2008/MV1008

240

MV1006/MV1012/MV1024/
MV2010/MV2020/MV2030/
MV2040/MV2048

60

Models with the /MC1 external
input channel option

If the measured/computed/external input
data is less than the specified number of
blocks, the MV transmits the available data.

Example Transmit two blocks of FIFO data from channels

1 to 10.

FFGET,001,010,2

Description • The FIFO buffer is a cyclic buffer, which

overwrites the oldest data. Use the FR
command to set the acquisition period.

• The MV transmits the specified number of

blocks (p4), starting with the block after the
previously read block.

Make sure to read the data within the following

buffer period to prevent data dropouts.
• MV1004
FIFO buffer size: 240 cycles (scan interval)
Maximum buffer period: 240 × (acquisition

interval). Resending is not
possible after the buffer
period elapses.

• Parameters p2 and p4 are valid when p1 is

set to GET.

• If p4 is omitted, the MV transmits all blocks.

4.8 Output Commands (Setting/Measured/Computed Data Output)