Yokogawa Standalone MW100 User Manual

Page 14

Advertising
background image

14/17

For scaling computation When (Value width/Span width) > 1, Value width is changed to within

the span width. For such settings, the resolution of values computed with scaling computation is
lower than Value Max/Value Min.

Value width

=

(Value Max–Value Min)

Span width

= (SpanMax–SpanMin)

Span

width

(max)

=

60000


Scaling computation accuracy: ±(zoom factor + 2) digits (zoom factor is Span width/Value width)

Ex) When

Value Min

= 0, Value Max = 1 000, Span Min = 0, Span Max = 10000

Accuracy = ±(10+2) digits = ±12 digits (no digits after the decimal point)



CAN protocol version: Ver. 2.0B (Standard & extended message format)
Supported standards:

ISO11898 (High Speed Communication)

Communication speed:

10 kbps–1 Mbps, Time quanta, and sampling points can be selected

Communication Speed Related Settings

Communication
speed (bps)

10 k, 20 k, 33.3 k, 50 k, 62.5 k, 83.3 k, 125 k, 250 k,
500 k, 800 k, 1 M, Other

Baud Rate Prescaler (BRP)

1–256

Synchronization Segment(SS)

1Tq (fixed)

Time Segment 1 (TSEG1)

4–16Tq

Time Segment 2 (TSEG2)

2–8Tq

ReSynchronization Jump Width (SJW)

1–4Tq

Detailed
settings

Bit Sample Point (BSP)

1 or 3


Byte order: Big Endian/Little Endian
Data types: Unsigned, Signed, Float (32-bit), Double (64-bit)

No. of CAN ports: 1
Termination (connector type): CAN (for measurement): D-Sub-9 PIN (male)

SERIAL (for settings): D-Sub-9 PIN (male)

Reference operating conditions: Ambient temperature: -20–50˚C

Ambient humidity: 20–80% when -20–40˚C

10–50% when 40–50˚C

Storage Environment: Storage temperature range: -25–60˚C

Storage humidity range: 5–95%

Power consumed: Approximately. 2 W