Yokogawa Standalone MW100 User Manual

Page 6

Advertising
background image

6/17

The relationship between the measurement interval and the maximum number of channels that can be set is the
same as that in the MW100 standard specifications (in the table below).

Measurement

Interval

Max. Number of Channels

Set

Notes

10 ms

10

10/50 ms mixed

10

50 ms

30

The max. number of channels that can be set refers to
the total number of valid input channels excluding
channels set to SKIP, and is applied across multiple
modules.

100 ms–

60

No restrictions


Precautions When Setting the Measurement Interval to 10ms(50ms)
All slots can be set to the 10ms(50) measurement interval. However, if the maximum number of channels that
can be set is exceeded, an error message will appear upon measurement start. (E223 “Too many
measurement channels.”)






Advertising