2-25

IM 04P01B01-61E

Configuring the Recorderr

1

2

3

4

Index

Measure Alarm Hysteresis

Sets the alarm hysteresis of measurement channels in the range of 0.0% (OFF) to 1.0%
of the recording span in 0.1 steps. The hysteresis applies to all high limit and low limit
alarms of measurement channels.

Math Alarm Hysteresis (Models with the Computation Function (/M1

Option))

Sets the alarm hysteresis of computation channels in the range of 0.0% (OFF) to 1.0%
of the recording span in 0.1 steps. The hysteresis applies to all high limit and low limit
alarms of computation channels.

Remote (Models with Remote Control Input (/R1 Option))

Remote 1 to Remote 5 corresponds to remote control input terminals 1 to 5. The
following functions can be assigned.

Display

Description

NONE

No function is assigned.

Record On/Off

Starts/stops recording.

Chart speed

Changes the chart speed.

Time adjust

Adjusts the internal clock to the nearest hour.

MATH start/stop

Starts/stops the computation on the computation function

(/M1 option).

MATH reset

Resets the computed result of the computation function

(/M1 option).

Manual print

Executes manual printout.

Alarm ACK

Executes alarm output release.

message #

Prints message # (where # is a value between 1 and 5).

Priority to Remote Recording*

Starts/stops recording.

Switching Batch Comment*

Switches between start printout and start printout 2. Or,

switches between end printout and end printout 2.

* Selectable on recorders with firmware version 1.31 or later and header printout (/BT1 option).

2.7 Setting the Items in Basic Setting Mode