4 connecting the power and energy meter and the pc, Serial communication connection – Yokogawa PR300 Power and Energy Meter User Manual

Page 8

Advertising
background image

<Toc> <Ind>

<1. Before Using the Software>

1-5

1.4 Connecting the Power and Energy Meter and

the PC

The following three methods are available for connecting the power and energy meter

and the PC.

Serial Communication Connection

(SG)

(B

+

)

(A

)

(B

+

)

(A

)

(FG)

Terminator

Short circuit

RS-485

RS-485

RS-485

Approx. 1200 m maximum (31 units maximum)

PC

ML2

RS-232C/RS-485

Converter

(Yokogawa)

RS-232C
straight
cable

PR300

UPM100
UPM101

PR300

UPM100
UPM101

PR300

UPM100
UPM101

Notes:
The PR300 employs a two-wire system for RS-485 communication.

SG: The SG terminal is connected to match the signal level of the RS-485 communication line.
FG: All shielded wires must be connected and then grounded at one place to provide noise protection for

RS-485 communication lines.

120 (built-in)

(A

)

(TERM)

(SG)

(SG)

(SG)

(B

+

)

(A

)

(B

+

)

*1

*2

*3

*1 120

Ω

externally connected (parts no.: L3035RK)

Use the resistor externally connected without using the built-in resistor of ML2.
Make resistance of the terminator the same as that of the resistor.
*2 When connecting the ML2, use it without returning an echo.
For details, refer to the ML2 RS232-C/RS-485 Converter User’s Manual (IM 77J04L02-01E).
*3 For the UPM100 and UPM101, 120

Ω

resistors are not built in.

Set the communication
method of PR300,
UPM100 and UPM101
to Modbus/RTU.

Figure1.2

Example of Serial Communication Connection

Ethernet Communication Connection (for the PR300 Only)

Ethernet

LAN
connection

HUB

IP address: 192.168.1.2

IP address: 192.168.1.3

PC
IP address: 192.168.1.1

Figure1.3

Example of Ethernet Communication Connection

IM 77C01Y01-01E