Model VJU7
Universal Temperature Converter
(Isolated Single-output and
Isolated Dual-output Types)

IM 77J01U07-01E

4. MODEL AND SUFFIX CODES

0/

Input signal
U: Thermocouple, RTD, mV signal

Output-1 signal
A: 4 to 20 mA DC
6: 1 to 5 V DC
Z: (Custom Order) DC current or voltage signal

Output-2 signal
A: 4 to 20 mA DC
6: 1 to 5 V DC
P: Communication function (RS-485)
T: Alarm output (2 relay contacts)
N: No output-2 signal

Power supply
6: 100-240 V AC/DC (Operating range: 85 to 264 V)
7: 15-30 V DC (Operating range: 12 to 36 V)

Number of outputs
1: 1 output
2: 2 outputs

Model

VJU7-0

-

Optional specification
Blank: With socket
/SN: Without socket
/RJCN: Without RJC sensor

1. CAUTIONARY NOTES FOR SAFE

USE OF THE PRODUCT

This user’s manual should be carefully read before installing
and operating the product. The following symbol is used on the
product and in this manual to eusure safe use.

WARNING

This symbol is displayed on the product when it is
necessary to refer to the user’s manual for infor-
mation on personnel and instrument safety. This
symbol is displayed in the user’s manual to indi-
cate precautions for avoiding danger to the opera-
tor, such as an electric shock.

The following symbols are used only in this manual.

IMPORTANT

Indicates that operating the hardware or software
in a particular manner may cause damage or result
in a system failure.

NOTE

Draws attention to essential information for under-
standing the operations and/or functions of the
product.

2. CHECKING PRODUCT SPECIFICATIONS

AND PACKAGED ITEMS

(1) Model and Specifications Check

Check that the model and specifications indicated on the
nameplate attached to the side face of the main unit are as
ordered.

(2) Contents of the Package

Check that the package contains the following items:

VJU7: 1

User’s manual (this manual: IM 77J01U07-01E): 1

Accessories:

Tag number label: 1 sheet

Range label: 1 sheet

RJC sensor (when /RJCN is not specified for the

optional specification): 1

3. GENERAL

This plug-in type Universal Temperature Converter receives
thermocouple, RTD or mV signal and converts it into isolated
DC voltage or current signal.

Settings of the input type (thermocouple, RTD or mV)
and measurement range can be changed within the
specified ranges.

One of DC voltage signal, DC current signal, communi-
cation function (RS-485) and alarm output (2 relay con-
tacts) can be selected for the output-2 signal.

Keep this manual in a safe place.

Network Solutions Business Divisiion

2-9-32, Naka-cho Musashino-shi, Tokyo 180-8750 Japan
Phone: +81-422-52-7179

Facsimile: +81-422-52-6619

IM 77J01U07-01E

©Copyright Nov. 1999
4th Edition: Feb. 2007