2 settings related to communication function – Yokogawa JUXTA VJU7 User Manual

Page 4

Advertising
background image

4

All Rights Reserved. Copyright © 1999, Yokogawa M&C Corporation

IM 77J01U07-01E

4th Edition Feb. 09, 2007-00

9.1.2 Input Hard Range

Select the input hard range from among AUTO, HIGH,
MIDDLE and LOW in D17: SELECT RANGE. In general, se-
lect AUTO.

AUTO: Sets the most appropriate input hard range auto-
matically with respect to the input range to be set.

HIGH: For RTD input, for a span of 130

or more in an

input range of 0 to 520

based on the reference

resistane table.

MIDDLE: For thermocouple or mV input, for a span of
27.5 mV or more in an input range of 10 to 100 mV con-
verted into thermoelectromotive force. For RTD input, for
a span of 38.5

or more in an input range of 0 to 176

based on the reference resistane table.

LOW: For thermocouple or mV input, for a span of 10
mV or more in an input range of -2.5 to 25 mV converted
into thermoelectromotive force.

NOTE

The conditions for the input hard range (HIGH,
MIDDLE and LOW) are specified for operations
within the range of accuracy rating. The input
range may be set to a range not meeting these con-
ditions, but take note of accuracy limitations. Simi-
lar accuracy limitations exist even when AUTO is
selected. For more information on accuracy limita-
tions, see the general specifications of VJU7 (GS
77J01U07-01E).

9.1.3 Input Range

Set the 0% value of input range in D22: INPUT1 L_RNG and
the 100% value of input range in D23: INPUT1 H_RNG nu-
merically within the following specified range.

Input type

Type K (CA)

Type T (CC)

Type E (CRC)

Type J (IC)

Type R

Type S

Type B

Type N

Type W3

*1

Type W5

*2

Pt100 (ITS-90)

Pt100 (IPTS-68)

JPt100 (JIS'89)

Pt50 (JIS'81)

mV signal

Operation guaranteed range

-200 to 1200

°

C

-200 to 350

°

C

-200 to 800

°

C

0 to 750

°

C

0 to 1600

°

C

0 to 1600

°

C

600 to 1700

°

C

-200 to 1200

°

C

0 to 2000

°

C

0 to 2000

°

C

-200 to 660

°

C

-200 to 660

°

C

-200 to 510

°

C

-200 to 649

°

C

-10 to 100 mV DC

Thermocouple input

RTD input

mV input

*1: W97Re3-W75Re25 (tungsten 97% rhenium 3%-tungsten 75% rhenium 25%)
The abbreviation of ASTM E988.
*2: W95Re5-W74Re26 (tungsten 95% rhenium 5%-tungsten 74% rhenium 26%)
The abbreviation of ASTM E988.

9.1.4 Direction of Output Action

When output 1 and output 2 are analog outputs, the outputs
can be reversed. Set the direction of output action in D38:
OUT1 DR (output 1) and in D39: OUT2 DR (output 2). Select
REVERSE for reverse action and DIRECT for direct action.

9.1.5 Wiring Resistance Correction

When an error occurs due to the influence of the input wiring
resistance, the wiring resistance can be corrected automati-
cally. Apply a stable input as shown below and select EX-

ECUTE in P01: WIRING R. The correction is also required
when the direction of burnout action is changed from UP
(DOWN) to DOWN (UP) or the wiring for input is changed.

VJ77

or

JHT200

Voltage

generator

mV Input

VJU7

Two signal lines are connected to
the same terminal of one side.

RTD Input

VJ77

or

JHT200

VJU7

Short-circuit at the cable end.

Thermocouple Input

VJU7

VJ77

or

JHT200

Short-circuit at the cable end.

9.2 Settings Related to Communication

Function

Set the following parameters when the communication func-
tion is specified for the output 2.
For more information on communication functions, see the
user’s manual for VJ Series Communication Functions (IM
77J01J11-01E).

9.2.1 Communication Protocol

Select the communication protocol from among PCLINK,
PCLINK WITH SUM, MODBUS ASCII, MODBUS RTU and
LADDER in F01: PROTOCOL.

9.2.2 Communication Address

Set the address number of the converter numerically in a
range of 1 to 99 in F02: ADDRESS.

9.2.3 Baud Rate

Select the baud rate from among 1200, 2400, 4800 and
9600 bps in F03: BAUD RATE.

9.2.4 Parity

Select the parity from among NONE, EVEN and ODD in
F04: PARITY.

9.2.5 Data Length

Select the data length from among 7 bits and 8 bits in F05:
DATA LEN.

9.2.6 Stop Bit

Select the stop bit from among 1 bit and 2 bits in F06: STOP
BIT.

9.2.7 Decimal Point Position

Number of decimals of input value (setting of D register
[D0003]) can be set. Select the number of decimals from
among 0 to 5 in F07: INPUT DEC PT.