- 13.2 -


Appendixes



C:\RHS Computer Files\Instructions\RHS\GB\642-40\0012B-01.doc 1997.09.11
RHS 900

Test - 1:

High pressure

8 - 9 bar

Low pressure

Approx.
0.8 bar


Fault/Problem Symptom

Possible

cause

Remedy

Unsatisfactory
refrigeration

Conditioned air not
cold

Air bubbles in sight
glass

Leakage in A/C unit


Insufficient refrigerant
in A/C unit

Locate leak and
repair

Replenish with
refrigerant

Test - 2:

High pressure

Approx.
20 bar

Low presure

Approx.
2.5 bar


Fault/Problem Symptom

Possible

cause

Remedy

Unsatisfactory
refrigeration

Insufficient

condenser

cooling

Fan does not run

Condenser performance
impaired by oil or dirt
deposits

Insufficient oil in A/C
unit (compressor fric-
tion)

Refrigerant overcharge

Clean condenser


Repair fan



Clean condenser



Replenish oil

check the refrigerant
quantity in the A/C unit -
empty the A/C unit,
evacuate and recharge thr
correct quantity



If none of these remedies
are successful, check the
refrigerant quantity in the
A/C unit - empty the A/C
unit, evacuate and
recharge

Test - 3: