- 13.3 -


Appendixes



C:\RHS Computer Files\Instructions\RHS\GB\642-40\0012B-01.doc 1997.09.11
RHS 900

High pressure

Approx.
7 - 15 bar

Low pressure

Approx.
1.5 bar


Fault/Problem Symptom

Possible

cause

Remedy

Periodic
disturbances in
A/C unit

Varying pressure on
high and low-pres-
sure sides

Moisture in A/C unit
causes ice formation on
expansion valve resul-
ting in reduced output,
ore filter drier
saturated.

Empty A/C unit,
evacuate and re-
charge. After the
recovery process,
replace filter drier.
If necessary, remove
expansion valve,
clean it and refit or
replace as necessary.




Test - 4:

High pressure

Approx.
6 bar

Low pressure

Approx.
-0.3 bar


Fault/Problem Symptom

Possible

cause

Remedy

Little or no
refrigeration from
A/C unit

Hoses before or af-
ter expansion valve
or filter drier cov-
ered with moisture
or ice

Expansion valve or
filter drier blocked with
ice because of moisture
in A/C unit

Disconnect A/C
unit, wait a few
minutes and then
empty the unit,
evacuate and
recharge