2. Electrical Service Specifications
* AWG Stranded Wire Type ... size wire as per National Electrical Code or local codes.
(Motor lead type wire is recommended).
IMPORTANT: The dryer must be connected to the electric supply shown on the data label that is
affixed to the left side of the top console behind the control door. In the case of 208
VAC or 230/240 VAC, the supply voltage must match the electric service
specifications of the data label exactly.
WARNING: 208 VAC and 230/240 VAC ARE NOT THE SAME. Any damage done to dryer
components due to improper voltage connections will automatically VOID THE
WARRANTY.
NOTE: ADC reserves the right to make changes in specifications at any time without notice or
obligation.
ADH-120
Reversing, 3ø (S
TEAM
)
ELECTRICAL SERVICE SPECIFICATIONS (PER DRYER)
IMPORTANT: 208 VAC and 230/240 VAC ARE NOT THE SAME. When ordering, specify exact voltage.
NOTES:
A. Fuse ratings are dual element, time delay, current limiting, class RK1 or RK5 ONLY.
B. Circuit breakers are thermal/magnetic (industrial) motor curve type ONLY. For others, calculate/verify correct breaker size
according to appliance amp draw rating and type of breaker used.
C. Circuit breakers for 3-phase (3ø) dryers must be 3-pole type.
SERVICE
VOLTAGE
PHASE
WIRE
SERVICE
APPROX.
AMP DRAW
MINIMUM
WIRE SIZE
FUSING
CIRCUIT
BREAKER
Dual Element
Time Delay
60 Hz
50 Hz
60 Hz
50 Hz
60 Hz
50 Hz
208
3ш
3/4
14.6
---
*
20
---
25
---
230/240
3ш
3
13.3
14
*
20
20
25
25
380
3ш
3/4
8
7.6
*
12
10
15
15
416
3ш
3/4
---
7.4
*
---
10
---
15
460
3ш
3/4
7.1
---
*
---
---
15
---
480
3ш
3/4
7.1
7
*
10
---
15
---
575
3ш
3
6.3
---
*
10
10
15
15