I/O Zone 583 (RHT, CAV, NMUA) - Examples of I/O’s
Options are in italics. Common options are bolded.
* Cost add option must be ordered to get multiplexing board
** Requires DC relay for single stage, UCS for multi-stage, or actuator for modulating control
*** A minimum of one keypad display must be ordered per project to set required set-points
**** A protocol will be a cost add option
Universal
Input
Jumper Setting
1
Supply Air Temperature (Monitor Only)
Thermistor/Dry Contact
2
Condenser Leaving Water Temperature
Thermistor/Dry Contact
3
Condenser Entering Water Temperature
Thermistor/Dry Contact
4
Cooling Coil Leaving Air Temperature Sensor
Thermistor/Dry Contact
5
Thermistor/Dry Contact
6
Load Shead*
Comp #1Q HP-5 Alarm*
Comp r#2Q HP-5Alarm
Thermistor/Dry Contact
7
Compr Lckt/Overflow
Comp #1 HP-5 Alarm
Comp #2 Alarm
Thermistor/Dry Contact
8
Emergency Shut Down External Clock (Start)
Dirty Filter (Switch Opt)
Thermistor/Dry Contact
Space or Return Humidity
Rnet
Jumper Setting
1
Room/Return Air Temperature (RS Std) or
Room Air Temperature/Stet-Point/Override (RS-Pro, Optional)
N/A
Analog
Output
Jumper Setting
N/A
1
Reheat**
0-10VDC
2
Water Side Economizer** 0-10VDC
3
Auxiliary Heat**
0-10VDC
Analog
Output
Jumper Setting
N/A
1
Supply Fan Start
Dry Contact for 24 VAC
2
Compressor Call #1
Dry Contact for 24 VAC
3
Compressor Call #2
Dry Contact for 24 VAC
4
Reversing Valve
Dry Contact for 24 VAC
5
Common Alarm
Dry Contact for 24 VAC