Figure 1, Warning, Connection of ranger 8 to premises wiring – Lincoln Electric IM604 RANGER 8 LPG User Manual

Page 22

Advertising
background image

15

15

RANGER 8 LPG

1. Install a double pole, double throw switch between

the power company meter and the premises
disconnect.

Switch rating must be the same or greater than
the customer’s premises disconnect and service
overcurrent protection.

2. Take necessary steps to assure load is limited to

the capacity of the Ranger 8 by installing a 35 amp
230V double pole circuit breaker. Maximum rated
load for the 230V auxiliary is 35 amperes. Loading
above 35 amperes will reduce output voltage

below the allowable -10% of rated voltage which
may damage appliances or other motor driven
equipment.

3. Install a 50 amp 115/230V plug (NEMA type 14-50)

to the Double Pole Circuit Breaker using No. 8,
4 conductor cable of the desired length. (The
50 amp 115/230V plug is available in the
optional plug kit.)

4. Plug this cable into the 50 amp 115/230V

receptacle on the Ranger 8 case front.

Figure 1

CONNECTION OF RANGER 8 TO PREMISES WIRING

230 Volt

60 Hz.

3-Wire

Service

POWER

COMPANY

METER

230 VOLT

115 VOLT

115 VOLT

LOAD

N

NEUTRAL
BUS

GROUND

PREMISES

DISCONNECT AND

SERVICE

OVERCURRENT

PROTECTION

GND

N

NOTE: No. 8 COPPER CONDUCTOR CABLE SEE

NATIONAL ELECTRICAL CODE FOR ALTERNATE WIRE

SIZE RECOMMENDATIONS.

230 VOLT

GROUNDED CONDUCTOR

35AMP

230 VOLT

DOUBLE

POLE

CIRCUIT

BREAKER

DOUBLE POLE DOUBLE THROW
SWITCH RATING TO BE THE SAME
AS OR GREATER THAN PREMISES

SERVICE OVERCURRENT

PROTECTION.

50 AMP, 115/230

VOLT PLUG

NEMA TYPE 14-50

50 AMP, 115/230 VOLT

RECEPTACLE

Connection of Ranger 8 to premises wiring must be done by a licensed electrician and must comply with
the National Electrical Code and all other applicable electrical codes.

WARNING