Figure 19 - Connection Terminals For The Infraducer.

8.2 Grounding

The rear panel on the INFRADUCER also has a connection for ground. The method of grounding depends on the method used

to mount the INFRADUCER.
1. If the INFRADUCER is mounted so that it is electrically insulated from the structure, connect the cable shield to the

ground terminal on the INFRADUCER and connect the other end of shield to ground at the power supply at the receiver

end.

2. If the INFRADUCER is mounted so that it is not insulated from the structure, do not connect the cable shield at the

INFRADUCER. Connect the cable shield only to ground near the power supply or receiver end. It is not necessary to

connect any wires to the INFRADUCER ground terminal.