Important information about this water heater, Installation checklist – American Water Heater 318935-003 User Manual

Page 16

Advertising
background image

16

Water Heater Location

Water heater location is important and can affect system
performance. Please check the following:

Installation area free of corrosive elements and

flammable materials.

Centrally located with the water piping system.

Located as close to the gas piping and vent pipe

system as possible.

Located indoors and in a vertical position. Protected

from freezing temperatures.

Proper clearances from combustible surfaces

maintained and not installed directly on a carpeted

floor.

Provisions made to protect the area from water

damage. Metal drain pan installed and piped to an

adequate drain.

Sufficient room to service the water heater. See

“Clearances and Accessibility” section of this

manual.

Water heater not located near an air moving device.

Is the installed environment dirty (excessive

amounts of lint, dirt, dust, etc.)? If so, the flame

arrestor located on the bottom of the water heater

will need to be cleaned periodically. Refer to the

“Maintenance of your Water Heater” section of this

manual for information on cleaning the flame-trap.

Combustion Air Supply and Ventilation

Check for sufficient combustion air supply. Insufficient air

for the combustion of gas will result in the flame becoming

“lazy”, thereby allowing the burner operating temperature

to decrease. This causes the gas control to shut off the

gas supply. Is the water heater installed in a closet or other

small, enclosed space? If so:

Are there openings for make-up air to enter and

exit the room/area?

Are the openings of sufficient size? Remember,

if there are other gas-fired or air-consuming

appliances in the same room, you need more

make-up air. Refer to the “Location Requirements”

section of this water heater manual for specific

requirements.

Fresh air not taken from areas that contain negative

pressure producing devices such as exhaust fans,

fireplaces, etc.

Is there a furnace/air handler in the same room

space as the water heater? If so, has a return air

duct system been attached that exits the room?

If so, check for leaks on the air duct system. If no

air duct system is present, correct immediately

by contacting a local Heating, Ventilation, Air-

Conditioning & Refrigeration (HVAC-R) authorized

service provider.

Fresh air supply free of corrosive elements and

flammable vapors.

Fresh air openings sized correctly with consideration

given to the blocking effect of louvers and grilles.

Ductwork is the same cross-sectional area as the

openings.

Vent Pipe System

Check for proper drafting at the water heater draft hood.

Refer to the “Checking the Draft” section of this manual for

the test procedure. If the procedure shows insufficient draft

is present, please check the following.

Draft hood properly installed.

Vent connectors securely fastened with screws and

supported properly to maintain six inch clearance.

Vent connector made of approved material and

sized correctly.

Vent pipe system installed according to all local

and state codes or, in the absence of local and

state codes, the “National Fuel Gas Code”, ANSI

Z223.1(NFPA 54)-current edition.

Flue baffle properly positioned in the flue tube.

Check the vent system for restrictions/obstructions

and check the vent termination height. Refer to the

“Air Supply and Ventilation” section of this water

heater manual for specific requirements.

Recheck for sufficient combustion air supply.

Water System Piping

Temperature and pressure relief valve properly

installed with a discharge line run to an open drain

and protected from freezing.

All piping properly installed and free of leaks.

Heater completely filled with water.

Closed system pressure build-up devices installed.

Mixing valve (when applicable) installed per

manufacturer’s instructions (see “Water Temperature
Regulation” section).

Gas Supply and Piping

Gas type is the same as that listed on the water

heater data plate.

Gas line equipped with shut-off valve, union, and

drip leg.

Adequate pipe size and approved pipe material.

An approved noncorrosive leak detection solution

used to check all connections and fittings for possible

gas leaks. If such a solution is not available, use a

mixture of dish washing soap and water (one part

soap to 15 parts water) or children’s soap bubble

solution. Bubbles forming indicate a leak. Correct

any leak found.

TEFLON

®

is a registered trademark of E.I. Du Pont De Nemours and Company.

Important Information About This Water Heater

This gas water heater was manufactured to voluntary safety standards to reduce the likelihood of a flammable vapor

ignition incident. The new technology used in meeting these standards makes this product more sensitive to installation

errors. Please review the following checklist and make any required installation upgrades or changes.

Questions? Reference the number on the cover of this manual for service information.

Installation Checklist

Advertising