10 p – Detcon TP-624C User Manual

Page 19

Advertising
background image

c)

ALARM 2 LEVEL From the programming menu scroll to the alarm 2 level listing. The menu item appears as:

“SET ALARM 2 LEVEL”.

Enter the menu by holding the programming magnet stationary over “PGM 1”

for 3 seconds until the display reads

“SET ALM2 @ ##PPM”

, then withdraw the magnet. Use the program-

ming magnet to make an adjustment to “PGM 1” to increase or “PGM 2” to decrease the display reading until

the reading is equal to the desired alarm set point. Exit to the programming menu by holding the programming

magnet over “PGM1” for 3 seconds, or automatically return to the programming menu in 30 seconds.

d)

Exit back to normal operations by holding the programming magnet over “PGM 2” for 3 seconds, or automati-

cally return to normal operation in 30 seconds.

3.9.2 Alarm Reset

An alarm condition will cause the applicable alarm to activate its corresponding relay and LED. If alarm 1, alarm 2, or fault

alarms have been programmed for latching relays, an alarm reset function must be activated to reset the alarms after an alarm

condition has cleared. To reset the alarms, simply wave the programming magnet over either “PGM 1” or “PGM 2”, momentar-

ily, while in normal operations mode and note that the corresponding alarm LED(s) turn off.

3.9.3 Other Alarm Functions

Alarms are factory programmed to be non-latching, de-energized; and to f ire under ascending gas conditions. The

fault alarm relay is programmed as normally energized which is useful for detecting a 24VDC power source failure.

All alarm functions are programmable via jumper tabs. Changing alarm functions requires the sensor housing to be

opened, thus declassif ication of the area is required. See section 3.5.4-e for details.

3.10 P

ROGRAM

F

EATURES

Detcon MicroSafe™ H2S gas sensors incorporate a comprehensive program to accommodate easy operator inter-

face and fail-safe operation. Program features are detailed in this section. Each sensor is factory tested, programmed,

and calibrated prior to shipment.

Over Range

When the sensor detects gas greater than its selected full scale range (20, 50, or 100 ppm), it will cause the display to f lash

“20/50/100 PPM H2S”

on and off.

Zero Fault

If the sensor does not clear to <10% of range in <5 minutes after completing a span calibration, the sensor will

enter into a calibration fault mode which will cause the display to alternate between

“ZERO FAULT”

and the sen-

sors current reading.

Range Fault

If the sensor fails the minimum signal change criteria, then a

“RANGE FAULT”

message will be displayed.

Open Heater Fault

If the sensor heater should fail and become electrically open, the display will indicate a fault:

“HEATER FAULT”.

System Fault

If the detector has an irrecoverable calculation error, the display will indicate:

“SYSTEM FAULT”.

Sensor Heater Voltage Fault

Approximately one minute after start-up, the sensor will check the heater voltage. Normal heater voltage is 5.25

VDC. If the voltage drifts from this value by more than ±.3V, the display will indicate a fault:

“HEATER

FAULT”.

Fail-Safe/Fault Supervision

Model TP-624C MicroSafe™ sensors are programmed for Fail-Safe operation. Any of the following fault conditions

will activate the fault relay, illuminate the fault LED, and cause the display to read its corresponding fault condition:

“RANGE FAULT”

,

“ZERO FAULT”

,

“HEATER FAULT”

, or

“SYSTEM FAULT”

. A “Heater Fault”,

Detcon Model TP-624C Hydrogen Sulfide Sensor PG.19

Advertising