Detcon TP-624C User Manual

Page 6

Advertising
background image

3.3 S

PECIFICATIONS

Method of Detection

Solid state metal oxide diffusion/adsorption

Electrical Classification

CSA-NRTL approved Class I; Groups B, C, D; Div. 1.

Response Time

T50 < 45 seconds, T80 < 90 seconds

Clearing Time

T80 < 90 seconds

Repeatability

± 5% FS

Range

0-20 ppm, 0-50 ppm, or 0-100 ppm

Operating Temperature

-40° to +175° F

Accuracy

± 5% FS

Sensor Warranty

10 year conditional

Power Consumption

Normal operation = 83 mA (<2 watt); Full alarm = 118 mA (<3 watts)

Output

3 relays (alarm 1, alarm 2, and fault) contact rated 5 amps @ 125 VAC, 5 amps @ 30 VDC;

Linear 4-20 mA DC

RS-485 Modbus™

Input Voltage

22-28 VDC

3.4 O

PERATING

S

OFTWARE

Operating software is menu listed with operator interface via the two magnetic program switches located under the

face plate. The two switches are referred to as “PGM 1” and “PGM 2”. The menu list consists of 3 items which

include sub-menus as indicated below. (Note: see the last page of this manual for a complete software f low chart.)

01.

Normal Operation

a) Current Status

02.

Calibration Mode

a) Span

03.

Program Menu

a) View Program Status

b) Set Alarm 1 Level

c) Set Alarm 2 Level

d) Set Calibration Level

e) Set Heater Level

f) Set Range

g) Linearize Sensor

3.4.1 Normal Operation

In normal operation, the display ref lects the current status of the sensor and gas concentration and appears as:

“0 PPM H2S”

. The mA current output corresponds to the monitoring level and range of 0-100 ppm = 4-20 mA.

Detcon Model TP-624C Hydrogen Sulfide Sensor PG.6