• LED C LD4: alarm sending to the VisorALARM.

ON: an alarm has been sent to the VisorALARM.

OFF: a response has been received to the sent alarm.

• LED D LD5: a bi-directional call to the alarm panel is in progress.

ON: there is a bi-directional call to the alarm panel. The LED located next to the

relays is off as the alarm panel has directly accessed the telephone line.

OFF: no bi-directional call in progress. The panel is operating normally.

II - 3. Jumper

The jumper labeled P1 operates by short-circuiting both pins with the supplied
berg header. This permits the following tasks:

a)

On device startup this permits you to configure the IPDACT-2(UD) with
the default configuration. For further information on how to activate the
default configuration, please see section IV.2.1.1.

b)

Keeping the P1 jumper short-circuited for a little more than a second
gives you access to the telephonic console. This permits you to
configure / monitor the IPDACT-2(UD) through a telephone connected to
the said IPDACT-2(UD). For further information, please see section
IV.2.

c)

Keeping the berg header short-circuiting the P1 jumper denies access to
the serial console. You can regain access to the console by open-
circuiting the P1 jumper.

IPDACT-2(UD) - Description

II-13

Doc.DM385-I

Rev. 4.0

II - 4. Connection points to the Control Panel and
external

In order to connect the IPDACT-2(UD) to the control panel and to power this,
there is a row of connectors. All the connections are limited in power. As can
be seen in the following figure, the connections are grouped in the following
manner:

Figure 11. Connectors

Connectors to the control panel