IPDACT-2(UD) - Configuration

III-19

Doc.DM385-I

Rev. 4.0

III - Configuration

NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING
JURISDICTION, AND OTHER INVOLVED PARTIES

This product incorporates field-programmable software. In order for the
product to comply with the requirements in the Standard for Control Units and
Accessories for Fire Alarm Systems, UL 864, certain programming features or
options must be limited to specific values or not used at all as indicated below.

Program
feature or
option

Permitted in UL
864? (Y/N)

Possible
settings

Settings permitted
in UL 864

Register 16

(Main Keep
Alive Interval)

N

0-90 seconds

1-90 seconds

Register 22

(Backup Keep
Alive Interval)

N

0-90 seconds

1-90 seconds