4 nfpa style 7 slc using isolator modules, Nfpa style 7 slc using isolator modules – Fire-Lite SLC Intelligent Control Panel Wiring Manual User Manual
Page 26

26
FireLite SLC Wiring Manual — P/N 51309:P1 10/12/2011
SLC Circuits with Isolators
NFPA Style 7 SLC Using Isolator Modules
4.4 NFPA Style 7 SLC Using Isolator Modules
Style 7 operation requires using isolator modules (or a combination of isolator modules and isolator
bases) before and after each device. Flanking each device with an isolator provides fault protection
to all other devices on the loop.
•
T-tapping is NOT allowed within the Style 7 wiring configuration.
•
When a detector base or pull station is used, install isolator modules on both sides of the
device.
•
Connections between isolator modules and the device they isolate must be “close-nippled”
conduit, within 3 feet (91.44 cm).