2 wiring a nfpa style d idc with an mmf-300, Wiring a nfpa style d idc with an mmf-300 – Fire-Lite SLC Intelligent Control Panel Wiring Manual User Manual
Page 35

FireLite SLC Wiring Manual — P/N 51309:P1 10/12/2011
35
MMF-300 Wiring Diagrams
Monitor Modules
5.3.2 Wiring a NFPA Style D IDC with an MMF-300
Connect the SLC wiring to the module terminals 1 (–) and 2 (+).
Each module takes one address on the SLC. Use the rotary switches on the module to set it to the
required SLC address. Refer to “Setting an SLC address for a Single Point Module” on page 32.
The figure below shows typical wiring for a supervised and power-limited NFPA Style D (Class A)
IDC using an MMF-300 module.
•
Refer to the Device Compatibility Document for compatible smoke detectors.
•
See “Power Considerations” on page 61 for information on supervising 24 VDC power.
S
L
C-id
cD1tp
H
.wmf
24 VDC
Four-wire
Detector Base
Heat
detector
SLC
MMF-300
IDC
24 VDC Power
Filtered, Regulated,
Resettable
From
Supply
To Next IDC
or
Supervision Device
Manual pull
station
Figure 5.10 Typical Style D IDC Wiring with an MMF-300