3 wiring a cmf-300 module, Wiring a cmf-300 module – Fire-Lite SLC Intelligent Control Panel Wiring Manual User Manual

Page 45

Advertising
background image

FireLite SLC Wiring Manual — P/N 51309:P1 10/12/2011

45

Wiring a CMF-300 Module

Control Modules

6.3 Wiring a CMF-300 Module

This section contains instructions and diagrams for wiring a Signaling Line Circuit with a
CMF-300 as a Notification Appliance Circuit (NAC).

6.3.1 Wiring a Style Y NAC (Two-Wire) with Addressable Control

Modules

A supervised and power-limited NFPA Style Y (Class B) NAC using a CMF-300 module. Polar-
ized alarm notification appliances are shown connected to the module in a two-wire configuration.
Refer to the Device Compatibility Document for compatible notification appliances and relays.

•

See “Power Considerations” on page 61 for information on monitoring 24 VDC power.

•

Each module can control 2 amps of resistive load (on electronic devices) or 1 amp of inductive
load (on mechanical bells and horns).

•

24 VDC power must be provided from a UL listed power supply for fire protection use.

•

A power supervision relay is required only on the last module of the power run.

•

Do not T-tap or branch a Style Y circuit.

•

Terminate the circuit across the last device using an End-of-Line Resistor 47K, 1/2-watt,
P/N SSD A2143-00 (ELR-47K in Canada).

•

Do not loop wiring under the screw terminals of any notification appliance. To maintain
supervision, break the wire run at each device.

CMF-300

NAC

24 VDC Nonresettable power

SLC

SL

C-n

ac

Y

.w

mf

Note: Module polarities are shown in alarm condition

NOTE: A power
supervision relay is
required only on the
last module of the
power run.

ELR

47K, 1/2-watt

24 VDC Notification

Appliances

Figure 6.2 NFPA Style Y Notification Appliance Circuit

Advertising