2 wiring a nfpa style d idc with an mmf-300-10, Wiring a nfpa style d idc with an mmf-300-10 – Fire-Lite SLC Intelligent Control Panel Wiring Manual User Manual

Page 38

Advertising
background image

38

FireLite SLC Wiring Manual — P/N 51309:P1 10/12/2011

Monitor Modules

MMF-300-10 Wiring Diagrams

5.4.2 Wiring a NFPA Style D IDC with an MMF-300-10

Connect the SLC wiring to the module terminals T5 as shown below.

Use the rotary switches on the module to set the base SLC address. Each module takes five alternat-
ing addresses on the SLC. The remaining module points are automatically assigned to the next four
higher addresses. (Example: 28, 30, 32, 34 and 36). Refer to “Setting an SLC address for a Multi-
Point Module” on page 33.

DO NOT set the lowest address above 150 (41 for the MS-9050UD, 90 for the MS-9200, MS-
9200UD, and MS-9200UDLS), as the other module points will be assigned to nonexistent
addresses.

The figure below shows typical wiring for a supervised and power-limited NFPA Style D (Class A)
IDC using an MMF-300-10 module.

•

Refer to the Device Compatibility Document for compatible smoke detectors.

•

See “Power Considerations” on page 61 for information on supervising 24 VDC power.

24 VDC Power
Filtered, Regulated, Resettable

24 VDC Four-wire
Detector Base

Manual Pull

Station

Heat

Detector

IDC
Out

MMF-300-10

SLC

IDC

Return

SL

C

-idcD3

.cdwmf

Figure 5.13 Typical Style D IDC Wiring with an MMF-300-10