AMX Heavy Duty DC Module RDM-HDC User Manual

Installation sheet

Advertising
background image

Installation Sheet

RDM-HDC Heavy Duty DC Module

2400 W, 0-12 VDC

The RDM-HDC Heavy Duty DC Module is a heavy-duty 2400 W module for
dimming of fluorescent ballast loads. It uses a 0 to 12 VDC current sinking
or sourcing for use with all four-wire ballasts. It is designed for use with the
RDA series of enclosures, in an AMX Lighting™ modular digital dimming
system. The module’s 120, 240, and 277 VAC ratings are CE, UL, and
C-UL approved.

RDM-HDC UL and C-UL Ratings

•

120 VAC, 50/60 Hz, 2400 W

•

240/277 VAC, 50/60 Hz, 2400 W

•

Control Out: 50 mA, 12 VDC

sourcing/sinking

Suggested Dimmed Loads

•

Four-wire dimmable ballasts

•

All low-voltage DC controlled ballasts

Specifications

•

Dimensions (HW): 10" x 2.75" (25.4 cm x 6.99 cm)

•

Non-phase dependant

•

Use wires rated at 75°C (167°F)

•

Torque terminals to 20 in-lbs. (2.3 N/M)

•

Max. wire size: 10 AWG (4 mm²)

•

Wire stripping length: 0.28" (7 mm)

•

Weight: 1.3 lbs. (0.590 kg)

•

BTU/hr: 150

•

Control current: 150 mA @ 12 VDC

Caution: Pre-Installation Notes

•

All Class 1 wiring must be connected to proper terminals.

•

All control wiring must be connected to proper terminals.

•

Disconnect power while installing or connecting the unit.

•

Keep top and bottom air vents clear at all times.

•

Use low-voltage wires with a 300 volt rating or greater.

•

Use field installed copper conductors.

•

All electrical ratings are for continuous duty.

•

For indoor use only.

•

Test loads for shorts before connecting.

•

This module may require extra power from the AXlink connection or an

external power supply connected to the control card.

Connecting the RDM-HDC to the AMX Lighting Master

Lighting Application Drawings

Warning: Failure to ground the ballast may cause ballast
failure

FIG. 1 RDM-HDC

Low-voltage control
wiring: 4-pin

Relay

+ out (LV)

- out (LV)

Neutral

Line in

Load

High

Low-voltage

voltage

connector to AMX
Lighting master
controller

Mounting
points

FIG. 2 Connecting the RDM-HDC and AMX Lighting Master

FIG. 3 RDM-HDC application wiring

Pin 4 (GND)

Pin 3 (RLY)
Pin 2 (DIM)

Pin 1 (+12 V)

RDM-HDC 4-pin module connector

1 (+)

2 (DIM)

3 (-)

GND

4-pin plug from RDM series module

Note: The 4-pin plugs from the module connector to the 4-pin
connector on the master (black plug cover facing up).

RDM-HDC

LOAD LINE NEUT CON

Ballast

Florescent Ballast

Neutral
Line in (HOT)

Load

Neutral

+

-

Low-voltage wire rated
to 300 V

Circuit breaker
panel