AMX Dual Zero Cross Module RDM-2ZC User Manual

Installation sheet

Advertising
background image

Installation Sheet

RDM-2ZC Dual Zero Cross Module

2400 W

The RDM-2ZC Dual Zero Cross Module is a dual 2400 W zero-cross relay
built for long term, reliable switching of electronic fluorescent ballasts, elec-
tronic transformers and incandescent lamps. It is designed for use with the
RDA series of enclosures, in an AMX Lighting™ modular digital dimming
system. The module's 120, 240, and 277 VAC ratings are CE, UL, and C-
UL approved.

RDM-2ZC UL and C-UL Ratings

•

120-277 VAC, 2400 W

•

240/277 VAC, 2400 W

Suggested Switched Loads

•

Incandescent

•

Electronic transformers

•

HID ballast

•

Electronic and magnetic ballast

Specifications

•

Dimensions (HW): 10.00" x 2.75" (25.40 cm x 6.99 cm)

•

Non-phase dependant

•

Use wires rated at 75°C (167°F)

•

Torque terminals to 7 in-lbs. (0.8 N/M)

•

Max. wire size: 10 AWG (4 mm²)

•

Wire stripping length: 0.28" (7 mm)

•

Weight: 2.0 lbs. (0.91 kg)

•

BTU/hr: 300

•

Control current: 45 mA per relay (90 mA total) @ 12 VDC

Caution: Pre-Installation Notes

•

All Class 1 wiring must be connected to proper terminals.

•

All control wiring must be connected to proper terminals.

•

Disconnect power while installing or connecting the unit.

•

Keep top and bottom air vents clear at all times.

•

Test loads for shorts before connecting.

•

Use low voltage wires with a 300 volt rating or greater.

•

Use field installed copper conductors.

•

All electrical ratings are for continuous duty.

•

For indoor use only.

•

This module may require extra power from the AXlink connection or an

external power supply connected to the control card.

Connecting the RDM-2ZC to the AMX Lighting Master

Lighting Application Drawing

FIG. 1 RDM-2ZC

Low-voltage control
wiring: 4-pin connector
to AMX Lighting master
controller

Zero cross relay A

Zero cross relay B

Line in (hot)

Load out

High-voltage
connections

Mounting
points

FIG. 2 RDM-2ZC connections

FIG. 3 RDM-2ZC wiring configuration

Pin 4 (GND)

Pin 3 (RLY)
Pin 2 (DIM)

Pin 1 (+12 V)

3 (-)

1 (+)

RDM-2ZC 4-pin module connector

4-pin plug from RDM series module

NOTE: The 4-pin plugs from the module connector to
the 4-pin connector on the master (black plug cover facing up).

Ballast

Circuit breaker
panel

Neon lights

(cold-cathode, on/off)

Neutral

Load

All neutrals are common
to the Neutral block in the
enclosure. Provide a
separate neutral for
each load.

(B) Load

(B) Line in (HOT)

Load

Neutral

Fluorescent Ballast

(A) Line in (HOT)

(A) Load

Safety ground

Advertising