AMX Zero Cross Module RDM-ZC50 User Manual

Installation sheet

Advertising
background image

Installation Sheet

RDM-ZC50 Zero Cross Module

6000 W

The RDM-ZC50 Zero Cross Module is a 6000 W solid-state zero-cross
relay built for extra large loads. It is designed for use with the RDA series of
enclosures, in an AMX Lighting™ modular digital dimming system. The
RDM-ZC50 module's 120 VAC and 277 VAC ratings are CE, UL, and C-UL
approved.

RDM-ZC50 UL and C-UL Ratings

120-277 VAC, 6000 W

Suggested Switched Loads

•

Incandescent

•

Electronic transformers

•

HID ballast

•

Fluorescent ballast

Specifications

•

Dimensions (HW): 10.00" x 2.75" (25.40 cm x 6.99 cm)

•

Non-phase dependant

•

Use 75°C (167°F) copper conductors only

•

Torque terminals to 16 in-lbs. (7.25 kg-m)

•

Max. wire size: 6 AWG; 14 AWG min.

•

Wire stripping length: 0.35" (9 mm)

•

Weight: 1.0 lb. (0.45 kg)

•

BTU/hr: 400

•

Control current: 45 mA @ 12 VDC

Caution: Pre-Installation Notes

•

All Class 1 wiring must be connected to proper terminals.

•

All control wiring must be connected to proper terminals.

•

Disconnect power while installing or connecting the unit.

•

Keep top and bottom air vents clear at all times.

•

Test loads for shorts before connecting.

•

Run all low-voltage and control wires away from heat producing parts

of the dimmer.

•

Each dimming circuit must have a separate neutral connection.

•

All electrical ratings are for continuous duty.

•

AC lighting loads only.

•

For indoor use only.

•

This module may require extra power from the AXlink connection or an

external power supply connected to the control card.

Connecting the RDM-ZC50 to the AMX Lighting Master

Lighting Application Drawing

FIG. 1 RDM-ZC50

Low-voltage control
wiring: 4-pin controller
to AMX Lighting master
controller

Zero cross relay

Line in (hot)

Load out

High-voltage
connections

Mounting points

FIG. 2 RDM-ZC50 connections

FIG. 3 RDM-ZC50 wiring configuration

Pin 4 (GND)

Pin 3 (RLY)
Pin 2 (DIM)

Pin 1 (+12 V)

3 (-)

1 (+)

RDM-ZC50 4-pin module connector

4-pin plug from RDM series module

NOTE: The 4-pin plugs from the module connector to
the 4-pin connector on the master (black plug cover facing up).

Ballast

Circuit breaker
panel

Neon lights

(cold-cathode, on/off)

Neutral

Load

All neutrals are common
to the Neutral block in the
enclosure. Provide a
separate neutral for
each load.

Load

Neutral

Fluorescent Lighting

Line in (HOT)

Load

Neutral

Advertising