KROHNE OPTISOUND 3010C 2wire EN User Manual

Page 10

Advertising
background image

1

2

Fig. 3: Min. distance to the max. level

1

Dead zone

2

Reference plane

Information:

If the product reaches the transducer, buildup can form on it

over a period of time and later cause measurement errors.

1

3

2

100%

0%

Fig. 4: Measuring range (operating range) and max. measuring distance

1

full

2

empty (max. measuring distance)

3

Measuring range

Gauge pressure in the vessel does not influence OPTISOUND

3010 C. Low pressure or vacuum, however, damp the

ultrasonic pulses. This influences the measuring result,

particularly if the level is very low. With pressures under -

0.2 bar (-20 kPa) you should use a different measuring

principle, e.g. radar or guided radar (TDR).

Pressure/Vacuum

10

OPTISOUND 3010 C - 4 … 20 mA/HART

Mounting

30503

-EN
-050914

Advertising