4.5 Wiring variants
4.5.1 Pt100 measuring inserts
Resistance thermometers are connected acc. to DIN EN 60751 in three different wiring variants.
Of the three, the 3-wire connection is the most frequently used in the industry:
Applications and features
• The 2-wire connection is used with short cable connections and minimal requirements for
accuracy.
• The 3-wire connection is the industry standard and largely eliminates the effect of supply
resistance.
• The 4-wire connection completely eliminates the distorting influences of the supply
resistance and guarantees minimal measuring uncertainty.
TR 100: Wiring depending on sheath diameter
TR 100: wiring
Figure 4-1: Double (top row) and single version (bottom row). From left to right: 2, 3 and 4-wire connection.
1 white
2 red
Diameter [mm] / [inches]
single Pt100
Double Pt100
3 / 0.12
2-, 3- or 4-wire connection
2-wire connection
6 / 0.24
2-, 3- or 4-wire connection
2-, 3- or 4-wire connection