Operation, 7 functions in detail, 1 definition of positions and zones – KROHNE OPTISYS SLM 2100 EN User Manual

Page 51

Advertising
background image

OPERATION

5

51

OPTISYS SLM 2100

www.krohne.com

03/2014 - 4002737302 - MA OPTISYS SLM 2100 R02 en

5.7 Functions in detail

5.7.1 Definition of positions and zones

Figure 5-7: Definition of zones and positions

1 Home position:

Home position:

Home position:

Home position: this position marks the home (or zero point position) of the sensor. After any change of the settings
and to calibrate the zero point for the level measurement, the sensor will always return to this position.

2 Start position:

Start position:

Start position:

Start position: this marks the position of sensor in which the sensor start from and returns during a normal operation.

3 Blind zone:

Blind zone:

Blind zone:

Blind zone: in this zone the concentration measurement is not active, in order to avoid wrong measurements due to
sunlight or other interferences, before the sensor is immersed into the water. You can prevent unwanted measure-
ment by setting this zone to be 0.3 m / 1 ft below the normal liquid surface.

4 Maximum immersion depth:

Maximum immersion depth:

Maximum immersion depth:

Maximum immersion depth: this is the maximum distance from the home position. The sensor will stop at this depth
if it detects no sludge. Note: the sensor might stop and return at a shorter distance if a rake height is set.

5 Measuring zone:

Measuring zone:

Measuring zone:

Measuring zone: in this zone the sensor delivers its measuring results and the output signal varies from 4...20 mA.
Note! In case that no start position is set, the measuring zone equals the maximum depth (4).

6 Measuring range:

Measuring range:

Measuring range:

Measuring range: distance liquid surface to bottom of the tank.

7 Fluff layer:

Fluff layer:

Fluff layer:

Fluff layer: fluff or sludge cloud. The concentration has to be set as “fluff”.

8 Sludge blanket:

Sludge blanket:

Sludge blanket:

Sludge blanket: the concentration has to be set as “sludge blanket”.

9 Bottom rake zone:

Bottom rake zone:

Bottom rake zone:

Bottom rake zone: here a possibly existing bottom rake operates. The top of this zone is the height where the sensor
always has to stop during lowering to avoid hitting the bottom rake. This has to be set as rake height

rake height

rake height

rake height in the menu.

10 Floating sludge:

Floating sludge:

Floating sludge:

Floating sludge: sludge which floats on the surface. To avoid wrong measurements the blind zone has to be set below

the floating sludge.