Technical data – KROHNE OPTISYS SLM 2100 EN User Manual

Page 70

Advertising
background image

7

TECHNICAL DATA

70

OPTISYS SLM 2100

www.krohne.com

03/2014 - 4002737302 - MA OPTISYS SLM 2100 R02 en

Inputs and outputs

General

All in and outputs are electrically isolated from the power supply.

Inputs

Control inputs: Three active

control inputs, not polarity

sensitive

U

out

= 8 VDC

I

out

= -10 mA

U

low

= <2 V

min I

typical

at 2 V = -8.7 mA

U

high

= >4 V

max I

typical

at 4 V = -6.8 mA

Operating modes

Control input 1: Rake guard

switch or external trigger

(switchable via Software)

Control input 2: Rake guard

switch or external trigger

(switchable via Software)

Control input 3: Maintenance

mode

Outputs

Current outputs

Two outputs (4...20mA), galvanic

isolated from power supply,

active mode

Output data

Current output A: level of fluff

Current output B: level of sludge

blanket or concentration (profile)

Operating data

U

max

= 18 VDC

I = 4...20 mA

I

max

≤ 22 mA

R

L

≤ 550 Ω

Relays

Operating modes

Relay 1 and 2: limit switch or

status output

Relay 3: pump protection

Operating data for all relays

U

ext

≤ 24 VDC/250VAC

I ≤0.3 A

.book Page 70 Wednesday, April 30, 2014 1:39 PM

Advertising